|
|
Scale Model Test for a
Distribution Piping
Helmut Knoblauch**, Roman Klasinc**, Guenther
Heigerth*, Wolfgang Sattler**
Department of Hydraulic Structures and Water
Resources Management
Graz Technical University, Stremayrgasse 10,
8010 Graz, Austria
Email:knoblauch@kwb.tu-graz.ac.at
* Professor and Head of the Department
** Associate Professors
Abstract
The
paper deals with model tests for a manifold of a hydropower station with 4
turbines installed, to determine relevant energy losses. Construction of model,
monitoring equipment and basic suggestions are discribed. Measurements and
evaluations at various load cases are presented and commented on, especially
the phenomenon of negative energy losses.
Keywords:
Model tests, manifold, energy losses
Introduction
In the spring of 1997, the Institute of
Hydraulic Structures and Water Resources Management was let a contract for
carrying out a hydraulic scale model test concerning the Kapichira manifold. The
client was VOEST Alpine MCE, designer of the steel structure and at the same
time the supplier of the structural steel elements.
The task of the Institute as the contractor was
to determine the energy losses incurred in the distribution piping (see fig.
1). For this purpose a plexiglass model was constructed to scale 1:26.43 at the
Institute's Hermann-Grengg Laboratory, and the appropriate measurements were
carried out and evaluated.
Design of the
Kapichira Manifold
The Kapichira power station will be equipped
with four turbines for power generation. Water will be fed to the turbines
through a steel-lined power tunnel. The steel lined section covers a straight
length of 68m followed by a bend and the 56m long distribution pipe system of
the manifold.
Water supply to the manifold is through a pipe
7.8m in diameter, which divides into four penstocks of 3.7m diameter each.
The first three legs branch off at angles of
42.28° (branch 1), 42.11° (branch 2), and 41.99° (branch 3). The deflection
angle of branch 4 is formed by a pipe bend with an angle of 87.00°. (Note: All
the above angles are values measured in the horizontal plane.) In the
longitudinal profile, the plane of the manifold is inclined at 1.97° to the
horizontal.
Purpose of the Scale
Model Test
The purpose of the hydraulic scale model test
was to determine the energy losses incurred in the distribution piping. For
this purpose a plexiglass model was constructed to scale 1:26.43. The model
included the straight intake line and the distribution pipe. Upstream of the
intake cross section as well as downstream of the legs of the manifold
appropriate additional lengths were provided in order ensure straight uniform
pipe flow for the pressure measurements. The manifold region is exactly defined
by the intake cross section and the four outlet cross sections.
The scale model test was intended to determine
the energy losses incurred in the legs of the manifold for an approach flow to
the manifold of Q = 270m³/s (operation of the four turbines at Q = 4 x
67.5m³/s). The region under study extended from the cross section at the intake
to the manifold (measuring plane B as shown in fig. 1) to the respective outlet
cross sections (measuring planes 1A, 2A, 3A, and 4A, as shown in fig. 1).
Test Set - up
4.1 Construction of the Model
The manifold model was constructed in
plexiglass to scale 1:26.43 so as to reproduce the prototype on the basis of
the drawings supplied by the Client (see fig. 1). The selection of the model
scale was determined by the dimensions of the plexiglass pipes available (150mm
in outside diameter and 140mm in inside diameter) for the outlet legs of the
junction. The remaining plexiglass pipe elements were manufactured at the
laboratory. The outside diameter of the inlet pipeline is 307.1mm, the inside
diameter 295.1mm. The wall thicknesses of the pipes vary between 5mm and 12mm. From
measuring planes 1A, 2A, 3A, and 4A, the three legs and the bend continue as
straight pipelines with an inside diameter of 140mm.
The legs of the pipe dividing system consist of
cone and cylinder elements. These were manufactured of plexiglass, which was
formed warm over wooden models, cut, and glued or welded.
Downstream of the respective branches,
plexiglass pipelines of appropriate diameter (D = 140mm), leading to the flow
meters, were provided to simulate gates and turbines. Electrically controlled
Howell-Bunger valves arranged downstream of the flow meters allowed infinite
variation of the respective flows.
Water supply to the model was from an overhead
tank and through piping systems.

Fig.1: Plan of model for Kapichira power
station (model scale, 1:26.43)
4.2 Acquisition of Instrument Data
4.2.1
Measuring Planes
As stipulated in the contract, the purpose of
our studies was to determine the energy loss incurred between the inlet cross
section (measuring plane B) above the distribution pipe and the respective
outlet cross sections (1A, 2A, 3A, and 4A). Each of these five measuring cross
sections was equipped with 8 measuring bores (D = 1.5mm) evenly distributed
over the circumference of the pipe wall.

Fig.2: Bores in a measuring cross section as
viewed in the direction of flow
Apart from the above measuring planes, the
measuring system included one upstream cross section and three cross sections
downstream of the junctions and four each further downstream in the outlet legs
to allow potentially required subsequent measurements.
4.2.2. Measured Values
The data measured comprised the head loss
incurred between two measuring cross section as well as flow. Since the two
values are functionally connected, particular care had to be exercised in
making the measurements.
4.2.2.1 Pressure Measuring
Pressure difference was measured by means of
inductive differential-pressuer transducers, which directly measured the
pressure difference between two measuring cross sections. The various measuring
points and cross sections were connected with the differential-pressure
transducer via a special change-over switch. The eight measuring points of a
cross section were interconnected by a closed circular pipe so as to balance
pressure variations within a cross section. On the basis of previous experience
and preliminary tests, a measuring period of 20 seconds for a scanning rate of
30 individual values per second was chosen. The measuring accuracy allowed for
in interpreting the pressure differences was 1mm.
4.2.2.2 Discharge Measuring
Flow was measured by means of magneto-inductive
precision flow meters which in combination with flow control through the
Howell-Bunger valves ensured very accurate flow adjustment. The measuring range
per branch was between 25 l/s and 75 l/s for a symmetrical approach flow to the
four branches. The differential pressure data was digitally logged on data
acquisition boards, stored on a PC, and appropriately processed.
Theoretical Basis
5.1 Similarity Laws
Similarity between scale model test and nature
conditions require geometrical and dynamic similarity.
Geometrical similarity exists for a model where all the geometrical
lengths (LN) of the prototype bear a constant ratio to the
respective lengths (LM) on the model. This ratio is termed the scale
factor (LR) of the model (LR=
LN/LM). For the model under study LR= 26.43.
Dynamic similarity signifies that the sequence
of flow processes on the model corresponds to that on the prototype. The flow
processes and, hence, the energy losses are largely governed by inertia and
friction forces. That means that the studies and the conversion of measured
data had to be based on Reynolds' law of similarity. Therefore, apart from the
geometrical similarity criterion, it was necessary to keep the Reynolds'
number, Re, equal for model and prototype.
ReN/ReM = 1
Reynolds' number is defined as the ratio of
inertia forces to viscosity forces:
![]()
where
v...... characteristic velocity [m/s]
D
..... diameter of pipe [m]
n ...... kinematic viscosity of water [m³/s]
(n = 1.01 x 10-6 m²/s;
water temperature T = 20°C).
The requirement of equal Reynolds' numbers can
be met only where the velocity on the model corresponds to the product of prototype
velocity and model scale.
![]()
(This applies to laboratory tests using the
same liquid and temperature on the model as on the prototype.)
As it is not possible, however, to accomplish
on a water-operated model the Reynolds range of the prototype, it is necessary
to conduct serial tests trying to operate the model to a point in the vicinity
of that Reynolds range from which the zeta value in the square law of loss
becomes constant. Where this is not possible, it is necessary to extrapolate
the results of the serial tests using a mathematical method.
On the model under study, the maximum Reynolds
values reached were Remax = 1.28 . 106 related to intake cross section B. Compared
to that, the prototype Reynolds values are ReNatur = 4.3 . 107,
for a flow of Q = 270m³/s.
5.2 The Hydraulic Situation
The total head loss (hv) in a pipe
dividing system is composed of the friction loss (hR) plus the local
head losses (hForm) resulting from the flow deflections.
hv = hR + hForm
An exact quantitative separation between
friction loss and local head loss is not possible due to interaction effects
between the two quantities. Instead, for transferring model results, the
friction loss is determined for equivalent straight pipe sections on the
assumption of a fully developed pipe flow and is then deducted from the total
head loss.
According to the above definition, the local
head losses are
hForm = hv - h R
The frictional head loss is expressed by the
equation:
![]()
where
li .....
dimensionless friction factor according to Prandtl/Colebrook
Li .....
length of sub-section i
Di .....
diameter or equivalent diameter of pipe section i
vi .....
flow velocity in pipe section i
The zeta value z, governing local head loss is defined
as
![]()
and generally becomes constant from a Reynolds
range Re >106 and, hence, independent of the Reynolds number.
Both head loss quantities are proportional to
the velocity head. Energetic comparision of two cross sections allows the
following relationship after Bernoulli to be established:
hV =
ve²/2g + dp - va²/2g
with the pressure head differences (dp) between
two cross sections being obtained by measurement.
Velocities ve and va were determined using the continuity equation (Qi = Vi . Fi).

Fig.3: Comparison of energy lines after
Bernoulli
Test Results
6.1 Energy Losses
The purpose of the scale model studies was to
determine the energy losses incurred in the manifold for a symmetrical
operation of the four turbines at a design flow of 4 times 67.5 m³/s.
As to the determination the energy losses on
the distribution pipe of the prototype, it should only be mentioned in this
context that the local head loss coefficient, z , is equal to the difference of the
kinetic share of loss between the two measuring planes and the net pressure
difference (after deduction of plexiglass friction) on the model. The absolute
value of this difference is so small (a few percent of the measured pressure differences),
however, that despite the maximum possible measuring accuracy applied it was
severely affected by the natural pressure variations as reflected in the
relatively large scattering of the results. For this reason three (branch 1)
and four measuring series (branches 2, 3, and 4) were run. Such a series
involved the simultaneous measurement of flow and pressure difference between
the two measuring cross sections for model flows of between 4 x 20 l/s and 4 x
75 l/s. One flow increment of 4 x 5 l/s yielded 12 points for the flow -
pressure difference function. These points were then used to determine - as
described above - a curve function using a mathematical balancing method and
deducting plexiglass friction. The total losses on the prototype are composed
of the local head losses as measured on the model and the calculated friction
losses for the steel pipe.
The table below is a list of the results of the
measurements (local head loss coefficient z with the resulting local head loss
hForm) and the analytical results (frictional head loss hR,
total head loss hv), with measuring cross section B being used for
reference in accordance with the provisions of the Contract.

6.2 Notes
6.2.1
Results from Branch 1
Branch 1 gives a mean local head loss of
0.249m. The mean total head loss is 0.292m.
6.2.2 Results from Branch 2 and Branch 3
The local head loss coefficients (z) determined from the four measuring
series give negative values for branches 2 and 3. Hence, negative quantities
also result for the local head losses. This fact, which may at first appear
impossible, can be explained as follows:
It is known from the relevant literature [2] and [6] that there is a certain interaction
among the branches connected in series in a distribution system: The total loss
incurred in the branches connected in series is not equal to the sum of the
losses occurring in the individual branches. In fact, the total loss decreases
as a function of the distances between the junctions. The shorter the spaces,
the lower the losses, and the reduction involved can be substantial. This
phenomenon is actually a result of the asymmentry of the velocity profile
behind the junction. The "boundary layer material" flowing at a lower velocity
is largely "absorbed" by the first branch. This causes the core flow in the
continuing pipe to be shifted towards the junction of the second branch. In
this way, flow towards the downstream branch is much more favourable. Due to
the shape of the velocity profile, the energy content of this core flow is
larger than its mean value. If it is mainly this core flow that reaches the
junction, then negative loss coefficients are no longer surprising.
The mean value of local head loss resulting
from the four measuring series for the 2nd branch is -0.055. With allowance
being made for the friction losses of the steel pipeline, a mean value of
0.011m is obtained for the total loss.
The mean value of local head loss resulting
from the four measuring series for the 3rd branch is -0.074m. With allowance
being made for the friction losses of the steel pipeline, a mean value of
0.031m is obtained for the total loss.
6.2.3 Results from Branch 4
The mean value of local head loss resulting
from the four measuirng series for the 4th branch is 0.085m. With allowance
being made for the friction losses in the steel pipeline, a mean value of
0.253m is obtained for the total loss.
Summary
The Kapichira power station will be equipped
with four turbines for energy generation. Water supply to the turbines is
through a steel-lined power tunnel. The steel lining covers a straight section
followed by a bend and the 56m long distribution system. Approach to the
manifold is through a 7.8m diameter pipe branching to four penstocks of 3.7m
diameter each.
This Report refers to the calculation of the
energy loss incurred in the four outlet legs of the manifold.The studies were
conducted on a plexiglass model constructed to scale 1:26.43. The model
reproduced the straight supply line and the four outlet legs. Appropriate pipe
sections were added upstream of the entrance cross section and downstream of
the branches of the manifold in order to accomplish well-developed turbulent
flow conditions for the pressure measurements.
By way of summary, it can be stated that the
distribution pipe upstream of the turbines of Kapichira power station shows
favourable magnitudes of energy loss, which allow the conclusion that
acceptance of the shape of the manifold by the water current is good. Visual
inspection using dye injections gave no perceptible separation phenomena.
References
[1]
HARB V.
Modellversuch und hydraulische Probleme der Verteilrohrleitung; Seminar AK
Konstruktiver Wasserbau 1988, TU Graz
[2]
CHRIST A.,
ALLMEN W.v. Strömungstechnische Erkenntnisse über Abzweigstücke von
Verteil-rohrleitungen. Escherwyss Mitteilungen 1/2 1980
[3] KOBUS H. Wasserbauliches Versuchswesen; Mitteilungsheft Nr. 4; Deutscher Verband für Wasserwirtsch. 1978
[4] KRESNIK E.: Kunststoffe im wasserbaulichen Versuchswesen und deren rauhig-keitsmäßige Erfassung; TU-Graz, 1965
[5]
MÜLLER W., STRATTMANN H.
Rohrreibungsverluste in Druckleitungen von Wasserkraftanlagen. Technische Rundschau Sulzer 3/1964
[6] MÜLLER W., STRATTMANN H. Druckverluste in Abzweigrohren Verteilleitungen; Technische Rundschau Sulzer 4/-1971
[7] PETERMANN F. Der Verlust in schiefwinkeligen Rohrverzweigungen; Mitteilungen des hydraulischen Institutes der TU München, 1929