IAHR, founded in 1935, is a worldwide independent member-based organisation of engineers and water specialists working in fields related to the hydro-environmental sciences and their practical application. Activities range from river and maritime hydraulics to water resources development and eco-hydraulics, through to ice engineering, hydroinformatics, and hydraulic machinery.
Log On
About IAHRDirectoryCommitteesMy IAHRNews & JournalseLibraryeShopEventsJoin IAHRWorld CongressDonate
spacer.gif
spacer.gif eLibrary
spacer.gif eLibrary
You are here : eLibrary : IAHR World Congress Proceedings : 36th Congress - The Hague (2015) ALL CONTENT : Special sessions : Fluid mechanics of chlorine disinfection for the hong kong harbour area treatment scheme
Fluid mechanics of chlorine disinfection for the hong kong harbour area treatment scheme
Author : J.H.W. LEE(1), S.N. CHAN(2), K.W. CHOI(3) & Q.S. QIAO(4)
ABSTRACT
To protect the water quality of nearby bathing beaches, chlorination disinfection has been provided to the treated sewage
in a major sewage treatment works in Hong Kong. A ten-percent sodium hypochlorite solution (specific gravity 1.2) is
injected in the form of multiple dense jets (from dosing pipes at two vertical levels) into the sewage cross flow in a flow
distribution chamber (FDC). Bench scale experiments show that higher chlorine concentrations will lead to significantly
higher chlorine demand. Thus, the mixing and transport of chlorine in the FDC plays an important role in the disinfection
efficiency and determining the effluent quality. It is essential to achieve rapid mixing of chlorine with the sewage in order to
achieve maximum disinfection efficiency in the chlorine contact culverts before discharge to the receiving water via a
tunnelled sea outfall.
The diurnal variation in the sewage inflow (8 - 22 m3/s) and tide level results in variation between pressurized and free
surface flow in the hydraulic system. Furthermore, to maintain a minimum water depth, an oblique weir is installed across
the middle section of the chamber ¨C leading to complex 3D flow patterns and uneven distribution of flow and chlorine
concentration downstream of the FDC.
Theoretical and experimental modelling of the internal hydraulics of the dosing unit revealed a curious distribution of dense
jet flows. Due to the large relative density difference between chlorine solution and sewage, the relative dosing flow
between the lower and upper pipes may undergo a ¡°flow switching¡± ¨C leading to sewage intrusion into the upper pipe when
the dosage flow is low.
The hypochlorite solution (100,000 mg/L) needs to be diluted to around 10 ¨C 20 mg/L for complete mixing. Using the
integral jet model VISJET, it is found that with the present two-level dosing unit design, a dilution of only 100 to 1000 is
achieved within the FDC at a distance of 10m. A CFD model is employed to study the complex interaction between the
multiple dense jets and the non-uniform ambient flow through the FDC. An improved dosing unit design with pre-dilution is
suggested and tested to give optimal initial mixing and higher residual chlorine concentration ¨C resulting in significant
savings of operation cost and energy.